renu

FIOD-PDP

Datasheet

 

 

Características
Low cost compact Profibus Digital I/O module with DIN rail mounting
Pluggable terminal block for Profibus communication
User definable Station ID through DIP Switches
High Speed Profibus DP Slave communication
LED indication for each Input and Output , Communication and Power ON
No configuration software required
Isolation between I/O and Comm port, I/O and Power Supply
Short circuit protection for Output

 

Especificaciones
Power -
Power 24V DC ±10%
Reverse Polarity Protection Yes
Power failure with stand time 20 ms
Communication Port Profibus DP
Power disspation  2.5 W
Power Input
From supply voltage

Max.100 mA (Approx.)@24VDC
Digital Inputs -
Number of inputs 16
Number of Terminals 48 (3 terminals / input channel)
Type of Terminals  Pluggable (3.81mm pitch)
Rated Input Voltage  24 VDC (Max is 30VDC)
Rated Input Current 5mA @ 24 VDC
Input Impedance 4.9 K
Logic ‘0’ Voltage -30 to 5V
Logic ‘1’ Voltage 13 to 30V
Input Response time 10mS
Digital Outputs (Transistor)
Number of outputs 16
Number of Terminals 32 (2 terminals / Output channel)
Type of Terminals Pluggable (3.81mm pitch)
Maximum Load current 500 mA
Voltage drop at ON 0.8V
Short circuit protection Yes
Switching frequency 100Hz (maximum)
Nominal Load -
      Ohmic 
      Lamp 
      Inductive

48 E, 12 W 
12 W
12 VA (12 H)
Isolation
Between channels and Internal Yes (Optical Isolation)
Between Power and Internal Yes (Inductive)
Profibus Baud Rate
Profibus Baud rate (Autodetect)
 
9.6k, 19.2k, 45.45k,  93.75k, 187.5 k, 500k, 1.5M, 3M,  6M,12M bit/s
Bus Protocol Profibus-DP
FREEZE compatibility Yes
SNYC compatibility Yes
Diagnostic function Yes
GSD File Supplied with the unit
BUS Address 0 - 99 Setting through DIP Switches
Temperature
Operating 0° to 60° C
Storage -20° to 80° C
Humidity 10% to 90% (Non condensing)
 
Mounting DIN rail mounting
Size 155 W x 102 H x 48 D mm
Immunity to ESD as per IEC61000-4-2
Immunity to Fast Transients as per IEC61000-4-4
Immunity to Radiated electromagnetic field as per IEC61000-4-3
 
Immunity to Conducted disturbances as per IEC61000-4-6
Surge as per IEC61000-4-5
Radiated emission as per EN61000-6-4

 

 

 

 Psg. D’Olot, 121 3er 1era - 17006 Girona - Telf. +34 972 98 73 98 / +34 938 40 25 24 - Fax .+34 938 40 25 03 - Mvl. +34 678 725 255 - info@aptus-hmi.com
Dynisco, weintek, Protech, Weg, Renu, Indusoft, Indumicro, Wachendorff, Xaloy